AO5020AL detection terminal dry contact input isolated safety barrier relay (one in one out, one in two out)
+
  • AO5020AL detection terminal dry contact input isolated safety barrier relay (one in one out, one in two out)

AO5020AL detection terminal dry contact input isolated safety barrier relay (one in one out, one in two out)

Isolate and convert the dry contact signal from the danger zone to output it to the safe zone. The output method is relay contact output, and reverse phase selection can also be performed. The input terminal, output terminal, and power supply terminal are isolated from each other, and have the function of detecting line faults. Can connect on-site equipment such as travel switches, limit switches, pressure switches, and liquid level switches.
  • Product description
  • Technical specifications
  • Product portfolio
    • AO5020AL detection terminal dry contact input isolated safety barrier relay (one in one out, one in two out)

    ◆ Performance Overview

    Isolate and convert the dry contact signal from the danger zone to output it to the safe zone. The output method is relay contact output, and reverse phase selection can also be performed. The input terminal, output terminal, and power supply terminal are isolated from each other, and have the function of detecting line faults. Can connect on-site equipment such as travel switches, limit switches, pressure switches, and liquid level switches.

     

    ◆ Panel indicator light

    Doppler FLOW METER brings you professional service

    CH: Output signal status indicator light (red and yellow dual color). When the signal is disconnected or short circuited, it will display in red; When the output circuit is closed, it is displayed in yellow.

     

    ◆ Usage environment

    Working environment temperature: -20 ℃ to+60 ℃

    Allowable relative humidity at work: 10% RH to 90% RH (40 ℃)

    Allowable atmospheric pressure during work: 80kPa~106kPa

    Allowable ambient temperature during storage and transportation: -40 ℃ to+80 ℃

     

     

     

     

  • ◆ Technical parameters

    Explosion proof grade: [Exia] IIC

    Dangerous area allows input signal: dry contact signal

    Line fault detection function (LFD): If the input current is less than 50 μ A, it is judged as input disconnection

    Input current>6mA, judged as input short circuit

    Output signal to safe zone: relay contact

    Relay contact capacity (resistive load): 125V AC, 0.5A; 24V DC、1A

    Relay action time:<20ms

    Input and output are reversed control settings: K1 is set to the ON side, and the input and output of the corresponding channel are reversed.

    K1 is set to side 1, and the input and output of the corresponding channel are in phase.

    K2 is set to the ON side and does not include a disconnection alarm output function (no LFD function).

    K2 is set to 2 sides and includes a disconnection alarm output function (including LFD function).

    Switch lifespan: over 100000 times Switching frequency:<10Hz

    Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, testing time 1min)

    Insulation resistance: ≥ 100M Ω (between input/output/power supply)

    Electromagnetic compatibility: EMC complies with IEC61000-4

    Doppler flow meter brings you professional service,ertification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST):

    Between terminals 9 and 10: Um=250V AC/DC Uo=10.5V, Io=13mA, Po=34mW

    ⅡC           ⅡB         ⅡA

    Co        1.6μF         11.7μF      52.5μF

    Lo        147mH         441mH       1000mH

    Power supply: DC 18-32V (typical value 24V DC)

    Power consumption: 24V DC power supply, single relay output of 0.7W

    DC 24V power supply, two relays output 1.0W

     

Message

If you have any needs, please feel free to contact us at any time.

Submit Now

Related Products

message

HOW CAN WE HELP ?

Get In Touch With Us!

%{tishi_zhanwei}%

Contact Us

Address:

No.36, Longhui Road, Wujin National Hi-Tech Industrial Development Zone, Jiangsu Province, China

Address:

Building 5 and 11, Fuzhou IoT Industrial Park, 

No. 12 Xingye West Road, Mawei District, Fuzhou City

Tel:

+86-13055728858

Email:

aotai03@fjautec.com      Mr. Zhou

aotai01@fjautec.com       Mr. Liao

aotai02@fjautec.com      Mr. Zhang

aotai04@fjautec.com      Mr. Chen

Email:

autec@163.com


Copyright © 2025 Fujian Aotai Automation Equipment Co., Ltd.,  All Rights Reserved.