AO5082 detection terminal thermal resistance input isolated safety barrier (one in one out, one in two out)
- Product description
- Technical specifications
- Product portfolio
-
- AO5082 detection terminal thermal resistance input isolated safety barrier (one in one out, one in two out)
◆ Performance Overview
Isolate and convert the thermal resistance signal from the hazardous area into a current/voltage signal for output to the safe area. The input end, output end, and power supply end are three terminal isolated, with functions such as online fault self diagnosis, making it an intelligent safety barrier product. Optional use of our company's dedicated handheld programmer for parameter modification or calibration (see Programmer User Manual for details).
◆ Output status during input fault
Doppler FLOW METER brings you professional service
Follow method: Unless otherwise specified by the user, regardless of the fault state of the input signal (open circuit, short circuit, reverse connection, over range), the output will follow the changes of the input signal within the full range, but the maximum value will not exceed 12.5% of the output range (for example, when outputting 4mA to 20mA, the small output can be 0mA and the large output cannot exceed 22mA).
-
◆ Technical parameters
Explosion proof mark: [Exia] IIC
The hazardous area allows input signals: two-wire and three wire heating resistors (Pt100, Cu100, Cu50, BA1, BA2, etc.). The signal type and range are determined at the time of ordering.
Lead resistance: ≤ 20 Ω/wire
Can output signals to the safe zone:
Current signal: 0 (4) mA~20mA; 0mA~10mA;
Voltage signal: 0 (1) V to 5V; 0V~10V;
Doppler flow meter brings you professional service
Load capacity:
Current: 0 (4) mA~20mA: ≤ 300 Ω; 0mA~10mA: ≤ 600 Ω
Voltage: 0 (1) V~5V: ≥ 1M Ω; 0 (2) V~10V: ≥ 2M Ω
Isolation transmission accuracy: ± 0.2% F • S (25 ℃± 2 ℃)
Response time: 2 seconds
Temperature drift:<30ppm/℃
Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, testing time 1min)
Insulation resistance: ≥ 100M Ω (between input/output/power supply)
Electromagnetic compatibility: EMC complies with IEC61000-4
Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): Um=250V AC/DC
9. Between terminals 11, between terminals 10 and 11: Uo=6.5V, Io=9.7mA, Po=15.8mW
ⅡC ⅡB ⅡA
Co 17.5μF 399μF 700μF
Lo 264mH 792mH 1000mH
Power supply: DC 18-32V (typical value 24V DC)
Power consumption: 24V DC, single output 0.4W
Two outputs of 0.6W
Message