AO5063 operating terminal voltage output isolated safety barrier (one in one out)
- Product description
- Technical specifications
- Product portfolio
-
- AO5063 operating terminal voltage output isolated safety barrier (one in one out)
◆ Performance Overview
Convert the current/voltage signals from the safe area into voltage signals through isolation and output them to the hazardous area. On site equipment such as electrical converters and valve positioners that can control hazardous areas. The three terminal isolation of input, output, and power supply has the advantages of fast response, low power consumption, and good temperature characteristics.
-
◆ Technical parameters
Explosion proof mark: [Exia] IIC
The safe zone allows input signals:
Current: 0 (4) mA~20mA; 0mA~10mA;
Voltage: 0 (1) V to 5V; 0V~10V;
Input impedance: ≥ 1M Ω load capacity: ≥ 1MΩ
Introduction to Hazardous Area 1 and Performance
Convert the current/voltage signals from the safe area into voltage signals through isolation and output them to the hazardous area. On site equipment such as electrical converters and valve positioners that can control hazardous areas. The three terminal isolation of input, output, and power supply has the advantages of fast response, low power consumption, and good temperature characteristics.
◆ Technical parameters
Explosion proof mark: [Exia] IIC
The safe zone allows input signals:
Current: 0 (4) mA~20mA; 0mA~10mA;
Voltage: 0 (1) V to 5V; 0V~10V;
Input impedance: ≥ 1M Ω load capacity: ≥ 1MΩ
Can output signals to hazardous areas: 0 (1) V~5V voltage signal
Isolation transmission accuracy: ± 0.2% F ∙ S (25 ℃± 2 ℃)
Temperature drift:< 30ppm/℃ output ripple:< 1mV
Response time: ≤ 0.2ms stabilization time: ≤ 0.2s
Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, test time 1min)
Insulation resistance: ≥ 100M Ω (between input/output/power supply)
Electromagnetic compatibility: EMC complies with IEC61000-4
Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): Um=250V AC/DC
Isolation type safety barrier at the operating end
9. Between 10 terminals: Uo=25.2V,Io=85mA,Po=536mW
ⅡC ⅡB ⅡA
Co 0.074μF 0.57μF 2.03μF
Lo 3.4mH 10.2mH 27.2mH
Power supply: DC 18-32V (typical value 24V DC)
Power consumption: 24V DC power supply, single output 0.6W
Output signal: 0 (1) V~5V voltage signal
Isolation transmission accuracy: ± 0.2% F ∙ S (25 ℃± 2 ℃)
Temperature drift:< 30ppm/℃ output ripple:< 1mV
Response time: ≤ 0.2ms stabilization time: ≤ 0.2s
Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, test time 1min)
Insulation resistance: ≥ 100M Ω (between input/output/power supply)
Electromagnetic compatibility: EMC complies with IEC61000-4
Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): Um=250V AC/DC
Between terminals 9,10: Uo=25.2V, Io=85mA, Po=536mW
ⅡC ⅡB ⅡA
Co 0.074μF 0.57μF 2.03μF
Lo 3.4mH 10.2mH 27.2mH
Power supply: DC 18-32V (typical value 24V DC)
Power consumption: 24V DC power supply, dual output 0.8W