AO5049 operating terminal current output isolated safety barrier (two in, two out)
- Product description
- Technical specifications
- Product portfolio
-
- AO5049 operating terminal current output isolated safety barrier (two in, two out)
◆ Performance Overview
Convert the current signal from the safe area into a 4mA to 20mA current signal through isolation and output it to the hazardous area. On site equipment such as electrical converters and valve positioners that can control hazardous areas. The three terminal isolation of input, output, and power supply has the advantages of fast response, low power consumption, and good temperature characteristics.
◆ Usage environment
Working environment temperature: -20 ℃ to+60 ℃
Allowable relative humidity at work: 10% RH to 90% RH (40 ℃)
Allowable atmospheric pressure during work: 80kPa~106kPa
Allowable ambient temperature during storage and transportation: -40 ℃ to+80 ℃
◆ Panel indicator light
PWR: Green power indicator light, always on when the instrument is working normally;
-
◆ Technical parameters
Explosion proof mark: [Exia] Ⅱ C
Dangerous area allows output signal: current signal
Can input signal to the safe zone: 4mA~20mA
Output load capacity: ≤ 500 Ω; If larger load capacity is required, please customize
Output ripple:<1mV
Isolation transmission accuracy: ± 0.2% F ∙ S (25 ℃± 2 ℃)
Temperature drift:<30ppm/℃
Response time: ≤ 0.2ms
Stability time: ≤ 2ms
Dielectric strength: ≥ 2500V AC (between input/output/power supply, leakage current 1mA, testing time 1min)
Insulation resistance: ≥ 100M Ω (between input/output/power supply)
Electromagnetic compatibility: EMC complies with IEC61000-4
Certification parameters of National Quality Supervision and Inspection Center for Instrumentation and Electrical Products (CQST): Um=250V AC/DC
9. Between terminals 10, 11, and 12: Uo=25.2V, Io=85mA, Po=536mW
ⅡC ⅡB ⅡA
Co 0.074μF 0.57μF 2.03μF
Lo 3.4mH 10.2mH 27.2mH
Power supply: DC 18-32V (typical value 24V DC)
Power consumption: 0.6W