• Product description
  • Technical specifications
  • Product portfolio
    • ADVRDV composite passenger well flowmeter
    Measurement principle
      The product utilizes a composite dual-mode sensor combining radar Doppler and ultrasonic Doppler to detect water flow velocity, while simultaneously monitoring water level variations through the integration of radar, hydrostatic pressure, and conductivity sensors, thereby calculating real-time flow rates in manholes. Designed with low maintenance requirements as a primary objective, this product fully leverages the advantages of non-contact flow measurement via radar in manhole flow monitoring scenarios, reducing the likelihood of sensor fouling. Ultrasonic contact measurement supplements velocity detection during high water levels. The coordinated operation of multiple sensors enables complementary strengths, making the system more adapt
    able to diverse working condition requirements.
     
      This type of sensor is more suitable for use in situations with relatively fast flow rates.
     
     
     
     
     
     
    ◆Main Features
    Dual-mode (ultrasonic and radar wave) flow velocity sensing, seamless (no blind
    zone) docking;
    Note the flow velocity boundary conditions: 0.05m/s~0.2m/s (non-contact radar fl
    ow velocity sensing);
    Unidirectional model (when using ultrasonic speed measurement, flow direction i
    s not recognized, outputting absolute values);
    Bidirectional flow model (identifies positive regurgitation, flow velocity and flow r
    ate carry positive/negative signs);
    Multi-mode water level (radar, static pressure, and conductivity) sensing (built-in
    flow velocity-dynamic pressure compensation);
     
    Output parameters: comprehensive flow velocity, comprehensive flow rate, comprehensive water level;
    Other parameters: single-mode flow velocity, flow rate, water level, status of each sensor;
    Top-mounted installation on horizontal pipes, enabling wellhead operations via brackets;
    Main unit features an alloy-plastic housing with excellent corrosion resistance, waterproofing, and impact
    resistance; potted sealing ensures no impact from temperature variations on sealing;
    Supports RS485 upgrade, enabling remote OTA when paired with the main unit;
    Top-mounted installation on horizontal pipelines effectively prevents sensor material buildup;
    Mounting brackets facilitate easy sensor fixation.
     
    ◆Application scenarios
      Specialized sensor for manhole flow measurement, suitable for remote monitoring of manhole flow velocity, water level, and flow rate
  •  

    Technical parameters:

    Flow velocity radarWater temperature rangepower consumption

    Flow rate range

    0.05~20.000m/s,Recommended operating conditions for speed measurement:>0.2m/s(Boundary flow velocity 0.05~0.2m/s)

    Flow velocity accuracy

    Ultrasonic: 1% ± 0.005m/s, Radar: 2% ± 0.01m/s

    Flow rate resolution

    0.001m/s

    Dead zone velocity

    Ultrasonic Unidirectional Type: 0~0.002m/s, Ultrasonic Bidirectional Type: -0.03~0.03m/s, Radar: -0.05~0.05m/s

    Flow Velocity Rader

    24G (operating frequency), CW, Antenna angle: 24 °× 12 °, radiated power EIRP: 20dBm, antenna gain: 18.5dB

    ultrasonic sensor

    3 beams, 2MHz, 5 ° angle

    Water level range

    0~10m(Radar+Static Pressure+Conductivity Composite Sensing)

    Water level accuracy

    0.2%FS±0.001m

    Water level resolution

    0.001m

    Water level radar

    120-125G, range: 0.15-40 meters (affected by RCS), FMCW, Antenna angle: 14 °× 10 °

    Water Temperature Range

    0-60℃

    Water temperature accuracy

    0.5℃

    Water temperature resolution

    0.1℃

    power supply

    8-15VDC,Typical values:12VDC

    output

    RS485.MODBUS.RTU

    Output damping

    can be set

    Power Consumption

    12VDC/150mA

    response time

    10s

     


     

     

  • ADVRDV composite passenger well flowmeter
    Instrument ModelADVRDVComposite Manhole Flowmeter
    Flow Velocity and Water Level0Flow Velocity: 0.05m/s~20m/s            Water Level: 0~10m
    Process Connection Accessories0Standard L-shaped 304 stainless steel bracket
    Power Supply/CommunicationE12VDC(RS485)
    Cable LengthA10 meters (standard configuration)
    B20 meters
    Ccustom length (*Note 3)
    Breather Valve Assembly0Without manhole breather valve assembly (*Note 1)
    1With manhole breather valve assembly + cable lead-out (*Note 2)
    2With manhole breather valve assembly + aviation connector (*Note 4)
    Model Selection ExamplesADVRDV - 0 - 0 - E -  A - 0
       
    *Note1Except when the customer does not require the manhole breather valve, this option shall also be selected when the ADVRDV is used in conjunction with the AOWXM stainless steel barrel;
    *Note2When using this product in a manhole, it is recommended to select the manhole breather valve assembly; however, the cable cannot be threaded through a pipe in this case, so please note this when selecting.
    *Note3The length of the cable led out from the breather valve is 0.5 meters, and self-extending of the cable is not supported;
    *Note4When the ADV is equipped with a portable handheld terminal, it must be equipped with the manhole breather valve assembly + aviation connector.

Message

If you have any needs, please feel free to contact us at any time.

Submit Now

Related Products

There is currently no relevant data available, please add it in the background!

message

HOW CAN WE HELP ?

Get In Touch With Us!

%{tishi_zhanwei}%

Contact Us

Address:

No.36, Longhui Road, Wujin National Hi-Tech Industrial Development Zone, Jiangsu Province, China

Address:

Building 5 and 11, Fuzhou IoT Industrial Park, 

No. 12 Xingye West Road, Mawei District, Fuzhou City

Tel:

+86-13055728858

Email:

aotai03@fjautec.com      Mr. Zhou

aotai01@fjautec.com       Mr. Liao

 

Email:

autec@163.com


Copyright © 2025 Fujian AUTEC Factory Automation Equipment Co., Ltd.,  All Rights Reserved.